Level 2 · Direct digital control

Read a points list from command to proof

18 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Classify physical and software points from the controller’s perspective.
  • Select independent evidence of a fan or valve response.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Read the point from the controller’s side

An analog input (AI) measures a range such as temperature. A binary or digital input (BI or DI) senses two states such as a contact. An analog output (AO) can request position or speed. A binary or digital output (BO or DO) can request start. A , calculated flow or occupancy mode can exist entirely in software. A network object with an input-like name can obtain its value from a different controller. Use the I/O schedule and object binding to find its origin.

Trace the whole proof chain

For a fan, distinguish the effective start , the drive’s run indication and delivered air. An auxiliary contact reports contactor state. A current switch responds to current. A duct differential switch changes at its configured pressure threshold. A traverse measures flow at a defined duct section. Each observation covers a different part of the path. A display can label an echoed command as , so check what drives the value.

What each point actually observes
  1. SF-CMD · request
  2. Drive run contact · status
  3. Shaft speed · movement
  4. Duct flow · delivered air

Normal operation

Example training conditions

  • The start output is On, the run input is On, the speed output requests 60% and the independent duct traverse reads 2,400 cfm.
  • Label the binary points as start and proof, the modulating point as the speed request and the traverse as a physical measurement.

Worked service example

The training AHU graphic says the supply fan is on. Several outlets have little air.

Recorded field evidence · training example

  • SF-CMD = On. Drive status contact = Closed.
  • Fan speed feedback = 70%. Measured duct airflow = 950 cfm.
  • Prior balanced airflow under matching conditions = 3,600 cfm.

The request and drive indication agree, but the duct result is low. Verify local rotation, dampers, filters and the measurement location. Relabeling the fan-status input cannot establish where the missing air went.

Field procedure

  1. Write down the tag, asset, unit, source and time.
  2. Find the effective output and inspect local feedback.
  3. Choose a measurement downstream of the suspected failure.

Hands-on exercise

Command two actuator positions. Record the measured terminal voltage and shaft witness at each position, then restore automatic control.

Two-endpoint actuator checkout

The approved submittal maps 2–10 V to 0–100% travel. At each endpoint compare the BAS request with the actuator terminal voltage and shaft witness mark. Return the point to automatic control.

Terminal voltage 4.80 V · shaft witness 35% after travelRecorded positions · None

Record the low and high terminal readings and return the output to automatic control.

Unit 1 service call

The BAS says the supply fan is on. Can you prove the building is receiving air?

Find an independent witness that air reaches the occupied area. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. A building schedule has changed to occupied, but the motor starter contact remains open. Which value is the next link after the schedule?
2. Which observation best establishes that air reached a particular supply branch?
3. An alarm is named FanProof and its sole source is a current switch. What can that input establish when properly adjusted?
4. The point is wired from a duct pressure transmitter to a local controller and represents readings from 0 to 2 in. w.c. Which type fits?
5. A new points list calls a discharge temperature setpoint an AI. Which document detail would establish its true origin?

Field takeaways

  • Classify input and output relative to the controller.
  • Choose proof downstream of the failure you are testing.

References and further reading

Technician handbook