System explorer

Original module 08 assessment

BAS Software and Graphics

Reconstruct what an operating system actually did using point identity, priority, schedules, events and recorded measurements.

Module examination

Pass at 80%.

1. Which set of points gives the strongest evidence of a slipped outdoor-damper linkage?
2. The asset name is correct but one sensor displays °C where the point list expects °F. Which check belongs first?
3. A fan loses proof for eight seconds between two one-minute samples. What does a flat trend establish?
4. A temporary P8 test ends. Which action allows the existing lower-priority schedule to regain control?
5. P8 is null, P10 is 35% and P16 is 80%. What is the effective value?
6. Proof drops at 14:01:07 and a continuous mismatch delay is 20 seconds. At what second past 14:01 would it first qualify if the mismatch persists?
7. A BACnet binary output has active entries OFF at priority 8 and ON at priority 10; its relinquish default is OFF. What follows when priority 8 is released?
8. A trend records every 60 seconds. A proof drops for 9 seconds between consecutive samples. What additional evidence would best establish its duration?