What you’ll learn
- Resolve graphic labels to their actual point identities.
- Distinguish a requested output, physical position and measured process response.
Before you start · 1 related lesson
0 of 1 prerequisites demonstrated. You can open this lesson at any time.Start with the drawing boundary
Locate the asset, flow direction, served space and upstream source before clicking a value. A tag such as Air-handling unit. Its fan and conditioning sections supply air to a building or part of it. -02.CLG-VLV describes an equipment context and local naming convention. Read the site's point list for the precise meaning, point type, units, normal mode and data source. A similar tag on another unit may point to a different valve arrangement or controller.
Ask what drives each symbol
A fan icon may follow start The effective instruction issued to a device. Compare it with actual travel, rotation or flow. , motor status or measured airflow depending on its binding. An actuator indication may come from a position transducer integrated into the actuator. That reading can follow its command even if the coupling to the damper blade slips. Evaluate the chain from command to travel to the intended change in fresh process measurements.
Navigate through the evidence
Open the point inspector from the equipment view, check engineering units and quality, then open a trend that spans at least one actuator stroke. Read the current override state and compare related independent points over the same timestamps. A grey symbol with a A previously valid sample whose age exceeds the application’s usable interval. Check timestamps and quality. calls for checking quality and age before interpreting its last displayed number as an operating condition.
- Graphic and asset ID
- Effective outdoor-air command
- Actuator and physical blade travel
- Mixed-air temperature or measured outdoor flow
Normal operation
Example training conditions
- At 09:12 the graphic and point table both show a current 35% damper command, and the position sensor reads 34%. A field observation confirms blade movement.
- The graphic and register may use the same data source. The independent blade observation checks a different part of the chain.
Worked service example
A graphic says the outdoor damper is open but the mixing section remains warm.
Recorded field evidence · training example
- Outdoor 48°F, return 75°F
- Command 85%, actuator indication 84%
- Observed blade near closed and stable mixed air 74°F
Command and actuator agree while the blade position and mixed-air response disagree. Inspect the actuator-to-blade linkage and confirm representative temperatures. The command percentage cannot establish the outdoor-air fraction.
Field procedure
- Verify equipment tag, units, time and point quality in the inspector.
- Record command, actuator indication and independent physical reading.
- Place all three on a common trend and document which relationship failed.
Hands-on exercise
Compare requested travel with the measured position and process response while the actuator moves. Identify the first point that stops following.
AHU actuator stroke and process response
Command at least 75% for ten simulated seconds and record the missing travel. Identify the fault, repair the virtual heating valve, and repeat the stroke. Compare the temperature trend before and after repair. Release the test command after the verified stroke.
HW-GPM · measured branch flow 0.0 gpm. BLR-01.DIST-T · available supply water 145.9°F.
Inspect trend samples
| Time (s) | Command (%) | Travel (%) | Flow (gpm) | DAT (°F) |
|---|---|---|---|---|
| 60 | 0.0 | 0.0 | 0.0 | 66.5 |
Unit 1 service call
The BAS says the supply fan is on. Can you prove the building is receiving air?
Find an independent witness that air reaches the occupied area. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Rooftop operating graphic
Inspect OAD-CMD from the cutaway, then compare its register entry with OAD-FB, OAD-POS and MAT.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Resolve each graphic to the actual point and source.
- Use independent process response to verify a move or start.