Scale a 4–20 mA signal12 mA is halfway through a linear 4–20 mA signal. On a duct pressure transmitter set for 0–2.5 in. w.c., that’s 1.25 in. w.c.
Duct pressure training example
(12 − 4) ÷ 16 × 2.5 = 1.25 in. w.c. The transmitter is in one-way pressure mode. For another linear range, enter the engineering values assigned to 4 and 20 mA, including any nonzero low endpoint.
Distinguish span from offset
A transmitter is configured for 0–100 psi. Its current agrees with a reference at both test pressures, but the BAS shows 13 psi at 10 psi and 73 psi at 70 psi. Both errors are +3 psi. Check the input offset. If the BAS reads 10 and 82 psi instead, its displayed span is 72 psi for a 60 psi change. Check the configured endpoints before applying a trim. Verify the correction at a third pressure and record the as-left readings.
Compare the input with the field reading
- The BAS shows 0.63 in. w.c.
- Read the raw current at the controller. If it sees 12 mA, check its input mode and both scaling endpoints against the transmitter. If the raw reading differs from the measured current, check the input channel and loop wiring first.
- The BAS shows 1.25 in. w.c., but the pressure looks wrong.
- Compare an independent manometer across the same high and low taps with the fan at the same speed. If the readings disagree, check tubing, port assignment and transmitter zero. If they agree, investigate the air system at that operating condition.
Measuring the loop
Opening a live current loop interrupts its signal and can change equipment operation. Use an approved test point or suitable mA clamp. Follow the equipment isolation procedure before breaking the circuit. On the Veris PX3, confirm pressure mode, direction, output type and selected range.
Compare the gauge, terminal current and controller’s engineering value to locate the first scaling error.