One zone keeps the entire AHU at high pressure
Air-handling unit · Airside systems · Advanced
Customer complaint
Most zones are satisfied, but duct-pressure reset remains at its upper limit. Investigate the persistent request before changing the AHU pressure limit.
Equipment and operating sequence
Illustrative trim-and-respond reset uses terminal airflow shortfall and damper position. VAV-12 was recently reconfigured; its documented airflow conversion is Q = K√ΔP, with consistent units and a commissioned K available. VAV-12's documented occupied minimum airflow is 700 cfm for this exercise, so its active target remains 700 cfm when no additional cooling is needed.
The connected training building uses VAV-01 to represent the terminal identified as VAV-12 in the dispatch record.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Duct-static target: maximum permitted 2.0 in. w.c.; measured static: 2.0 in. w.c.
- Eleven VAV boxes are satisfied with dampers below 40%.
- VAV-12 reports 300 cfm against a 700-cfm target, damper 100%, and persistent pressure requests.
- The AHU has no fan alarm; VAV-12's zone is cooler than its setpoint.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Supply fan · case readings
- Duct static Reading
- 2.0 in. w.c.
- Duct static target Setpoint
- 2.0 in. w.c.
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Duct static | Reading · Supply fan | 2.0 | in. w.c. | — | — | — | — |
| Duct static target | Setpoint · Supply fan | 2.0 | in. w.c. | — | — | — | — |
| VAV-12 airflow | Feedback · Duct / zones | 300 | cfm | — | 300 | — | — |
| VAV-12 airflow target | Setpoint · Duct / zones | 700 | cfm | — | — | — | — |
Intake observations
- Duct-static target: maximum permitted 2.0 in. w.c.; measured static: 2.0 in. w.c.
- Eleven VAV boxes are satisfied with dampers below 40%.
- VAV-12 reports 300 cfm against a 700-cfm target, damper 100%, and persistent pressure requests.
- The AHU has no fan alarm; VAV-12's zone is cooler than its setpoint.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| AHU | The AHU has no fan alarm; VAV-12's zone is cooler than its setpoint. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.