Skip to workspace
BAS Bridge
System explorer

Level 6 · Building automation capstone investigations

Airside dispatch · persistent duct pressure requests

34 minutes · Advanced

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Distinguish a valid request from a correct measurement.
  • Trace one terminal's effect on an entire air handler.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

A request is a consequence

An can follow its pressure reset perfectly while wasting fan power. Trace which terminal generates the persistent request and what local conditions generate it. A real critical zone can need more pressure. A wrong sensor conversion can create the same requests with generous actual airflow. Compare this box with unaffected peers at a matched time.

Prove both sides of a correction

Validate the underlying measurement against an independent reference and the approved conversion. Preserve the zone's actual target and design minimum. After correction, check that the box satisfies its own load, other boxes retain delivery and the central target responds at the programmed reset interval. The pressure target can remain high briefly even after requests disappear.

Terminal demand reaches the fan
  1. Measured terminal flow
  2. Local flow shortfall
  3. Pressure request
  4. AHU target and fan
  5. Remaining zone delivery

Normal operation

Example training conditions

  • During a reference period the terminal receives its requested airflow, the damper responds to changes and the central pressure reset stays within its programmed bounds.
  • Record the terminal measurement together with the upstream target before judging the behavior of the airside system.

Worked service example

The supply fan remains near its upper pressure limit while most dampers are nearly closed.

Recorded field evidence · training example

  • One zone creates persistent pressure requests.
  • The AHU reaches its commanded duct pressure.
  • Peer terminals report acceptable airflow.

Investigate that zone's actual air delivery and its configured measurement before changing the AHU limits.

Field procedure

  1. Compare one terminal's indicated flow with its independently measured delivery.
  2. Calculate the relationship and corroborate it against the commissioning record.
  3. After correction, compare terminal delivery and common pressure behavior over the reset interval.

Hands-on exercise

Investigate the pressure-reset case, document the terminal discrepancy and verify the cross-system response.

Dispatch record

The AHU is maintaining 1.8 in. w.c. at the upper reset limit. VAV-7 keeps requesting more pressure while eleven peers meet their targets. The approved sequence trims its pressure target after five request-free minutes.

As-found inspection
Diagnostic finding

Unit 12 service call

Three open dispatches need field evidence and a closeout.

Support a diagnosis, rule out an alternative and document verified recovery across systems. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. Which result verifies the system-level effect?
2. Most zones meet airflow target while one requester is at 98% damper command. Which measurement distinguishes a real starved terminal from a bad airflow indication?
3. A terminal requests 500 cfm and independently measured delivery is 475 cfm. What is the shortfall as a percentage of the request?
4. A box reports 200 cfm. A calibrated hood measures 600 cfm. What is measured flow divided by reported flow?
5. After correcting the terminal indication, which trend pair best tests whether the upstream reset still serves the building?

Field takeaways

  • Trace a central symptom to the originating zone.
  • Verify local demand and common equipment response together.

References and further reading

Technician handbook