Level 6 · Building automation capstone investigations

Plant dispatch · cold perimeter on a hot header

35 minutes · Advanced

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Separate plant temperature, branch flow and terminal heat delivery.
  • Use matched-flow pressure witnesses and recovered heat output to verify the repair.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Locate where heat delivery breaks

Start with the served zones and the plant header. Hot water available at the header says little about the mass flow through a distant coil. Compare one healthy branch and one affected branch. Measure local inlet and outlet temperatures and flow. Use pressure taps on either side of individual devices to find the part consuming the available differential.

Compare comparable operating points

Pressure drop depends strongly on flow, fluid and component position. A large difference from a known clean reference at matched flow is more informative than a value taken at an unrelated pump speed. After local service, verify normal branch flow and heat delivery at the required load. Check the unaffected branch still works and that the plant returns to its scheduled operating target.

Perimeter heat delivery
  1. Boiler header and pump
  2. Branch pressure taps
  3. Valve, strainer and coil
  4. Local water flow
  5. Discharge air and zones

Normal operation

Example training conditions

  • With heating demand present the branch valve travels, water flows through the coil, the water cools across the coil and the discharged air warms.
  • Compare the branch flow and water temperature difference with the available header temperature under steady load.

Worked service example

Two perimeter zones lose heat while the interior branch remains warm.

Recorded field evidence · training example

  • The plant header is at its active target.
  • Both affected terminal controllers request heat.
  • The interior branch is operating at the same header temperature.

The common header observation supports a branch-level investigation. Obtain local measurements before attributing the fault to the boiler or control program.

Field procedure

  1. Compare branch delivery with the common header and the unaffected zone.
  2. Measure local differential and compare with the supplied baseline at the same flow.
  3. Witness restored coil heat transfer and normal neighboring service at comparable load.

Hands-on exercise

Investigate the branch complaint and use a measured post-repair heat rate to close the dispatch.

Dispatch record

Two perimeter zones share one heating coil and are cold at occupied load. The header is at its 160°F target and another branch is heating normally. The affected coil needs at least 80,000 Btu/h at this test load.

As-found inspection
Diagnostic finding

Unit 12 service call

Three open dispatches need field evidence and a closeout.

Support a diagnosis, rule out an alternative and document verified recovery across systems. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. An operating perimeter coil receives water at 143°F and returns it at 131°F. What is the supply-minus-return difference?
2. The branch warms after a correction, but only during a manual pump command. What must be checked before declaring recovery?
3. Why collect a clean strainer baseline at the same branch flow?
4. Using 500 × gpm × ΔT for ordinary water in this exercise, what heat rate does 8 gpm at 15°F drop deliver?
5. A common hot-water header is at target and one branch remains cold. Which measurement most directly tests that branch's ability to deliver heat?

Field takeaways

  • Trace both hydraulic delivery and thermal response.
  • Validate a repair at the load and operating conditions that caused the complaint.