Select the relationship, confirm its assumptions and carry the units through a worked example.

Conversions used in service investigations

Conversions used in service investigations
RelationshipExample and boundary
Ohm’s law · V = I × R12 mA × 250 Ω = 0.012 A × 250 Ω = 3 V across that resistance.
Linear scaling · y = y₁ + (x − x₁)(y₂ − y₁)/(x₂ − x₁)8 mA on 4–20 mA scaled 0–100 psi gives 25 psi.
Duct flow · Q = average velocity × clear area600 ft/min × 2 ft² = 1,200 cfm. Use an appropriate traverse and clear inside dimensions.
Fixed flow pickup · Q₂/Q₁ = √(Δp₂/Δp₁)A calibrated pickup at the same density gives half its original flow when measured differential falls to one quarter.
Fan affinity · Q ∝ N, Δp ∝ N², shaft power ∝ N³At 80% shaft speed, comparable points predict 80% flow, 64% pressure and 51.2% shaft power for the same fan and density.
Water heat transfer · Q̇ = ṁ cₚ ΔTFor ordinary liquid water near room temperature, 10 U.S. gpm × 10°F × approximately 500 ≈ 50,000 Btu/h. Use actual density and heat capacity for glycol.
Electrical energy · kWh = average kW × hoursA drive averaging 6 kW for 3 hours consumes 18 kWh. A one-time kW observation alone cannot establish monthly use.
Temperature · °F = °C × 9/5 + 3220°C equals 68°F. A temperature difference of 5°C equals a difference of 9°F.

Field example

A fan command falls to half speed and measured electrical input stays high. Confirm actual shaft speed, damper position, system resistance and the point where power was measured before using a power ratio.