Measurements
Engineering formulas and units
Select the relationship, confirm its assumptions and carry the units through a worked example.
Conversions used in service investigations
| Relationship | Example and boundary |
|---|---|
| Ohm’s law · V = I × R | 12 mA × 250 Ω = 0.012 A × 250 Ω = 3 V across that resistance. |
| Linear scaling · y = y₁ + (x − x₁)(y₂ − y₁)/(x₂ − x₁) | 8 mA on 4–20 mA scaled 0–100 psi gives 25 psi. |
| Duct flow · Q = average velocity × clear area | 600 ft/min × 2 ft² = 1,200 cfm. Use an appropriate traverse and clear inside dimensions. |
| Fixed flow pickup · Q₂/Q₁ = √(Δp₂/Δp₁) | A calibrated pickup at the same density gives half its original flow when measured differential falls to one quarter. |
| Fan affinity · Q ∝ N, Δp ∝ N², shaft power ∝ N³ | At 80% shaft speed, comparable points predict 80% flow, 64% pressure and 51.2% shaft power for the same fan and density. |
| Water heat transfer · Q̇ = ṁ cₚ ΔT | For ordinary liquid water near room temperature, 10 U.S. gpm × 10°F × approximately 500 ≈ 50,000 Btu/h. Use actual density and heat capacity for glycol. |
| Electrical energy · kWh = average kW × hours | A drive averaging 6 kW for 3 hours consumes 18 kWh. A one-time kW observation alone cannot establish monthly use. |
| Temperature · °F = °C × 9/5 + 32 | 20°C equals 68°F. A temperature difference of 5°C equals a difference of 9°F. |
Field example
A fan command falls to half speed and measured electrical input stays high. Confirm actual shaft speed, damper position, system resistance and the point where power was measured before using a power ratio.
Practice and related lessons
Technical references
- Fluke · Gauge, absolute and differential pressure
- TSI · Duct traversal for average air velocity and volume
- Spirax Sarco · Principles of flowmetering
- U.S. DOE · Fan system affinity laws
- Siemens · Configuring controller I/O
- Fluke · Measuring a 4–20 mA loop signal
- ASHRAE · Guideline 36-2024 title, purpose and scope
- ASHRAE · Guideline 36-2018 addendum x, chilled-water plant control
- U.S. Department of Energy · Energy-efficient commercial boilers
- Trane · Condenser water system savings
- Trane · Engineers Newsletter, primary-secondary and variable-primary flow examples
- Johnson Controls · Variable-speed primary chilled-water minimum-flow control