What you’ll learn
- Trace one input from its field tag to its displayed object.
- Separate span, offset and point-mapping errors using independent measurements.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Work outward from a known input
Find the sensor tag, physical input channel, signal range, units and object identifier in the approved points list. Record the as-found value. Apply a known simulated input, watch the raw channel and follow the change to the controller value and operator graphic. If a different zone responds, the wiring or binding can be wrong even when the displayed number looks reasonable.
Test more than one condition
A single midscale reading can conceal a reversed range or a fixed display value. Use low and high references, then an intermediate point to check linearity. For a temperature sensor, use its specified curve and a colocated reference allowed to stabilize. Record reference accuracy and the project tolerance before adjusting calibration. A corrected display offset cannot repair a wrong sensor curve.
- Device tag and reference
- Controller terminal and raw signal
- Scaled object and units
- Graphic with matching timestamp
Normal operation
Example training conditions
- With the project input range at 4–20 mA for 0–100 psi, a 12 mA simulator at the identified input produces 50 psi at the local controller and at the matching graphic tag.
- Signal injection checks the channel and mapping. Reconnect the original sensor and verify its measured process before closeout.
Worked service example
Two duct transmitters pass a visual check at zero pressure.
Recorded field evidence · training example
- Transmitter span 0–2 in. w.c. at 4–20 mA.
- At 12 mA the local reference is 1.00 in. w.c.
- AI-3 shows 1.00. The graphic reads 0.00 and changes when AI-4 is tested.
AI-3 scales correctly at the tested condition. The graphic responds to another input. Trace its binding before calibrating either device.
Field procedure
- Match the terminal and object to the approved submittal.
- Capture low and high references with time and units.
- Check an intermediate reading, compare error with tolerance, then restore service.
Hands-on exercise
Run the low and high point checks and compare both readings to the expected endpoints.
Two-endpoint actuator checkout
The approved submittal maps 2–10 V to 0–100% travel. At each endpoint compare the BAS request with the actuator terminal voltage and shaft witness mark. Return the point to automatic control.
Recorded positions · NoneRecord the low and high terminal readings and return the output to automatic control.
Unit 10 service call
A checkout point moves in the wrong direction under load.
Leave a reproducible point-to-point, functional and restoration record. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
AHU point register
Open an analog input, record its object identifier, engineering units and model range, and locate the matching tag on the equipment graphic.
Open simulator →Knowledge check
Pass at 80%. Every safety item must also pass.
Field takeaways
- Prove point identity and range separately.
- Keep the reference, displayed response and acceptance tolerance together.
References and further reading
- DOE FEMP · Commissioning for Federal Facilities ↗
- BACnet Committee · Objects, Properties and Services ↗