Module examinationPass at 80%. 1. A training reset target is 1.36 in. w.c., with an upper limit of 1.40. A qualified request adds 0.10. What target reaches the inner fan loop?Answer (in. w.c.)2. With outdoor air at 45°F and return air at 75°F, what is the ideal mixed temperature at 40% outdoor air?Answer (°F)3. An optimal-stop trial saves half an hour of cooling but a late-occupied zone exceeds its limit. What should the comparison include?Only the fan's stop timeOnly whether the schedule button says AutoActual occupancy, zone drift, ventilation obligations and the approved comfort band4. Several coils meet their targets. One is fully open with very low measured branch flow while plant supply temperature is correct. Which evidence comes next?Differential pressure across that branch and valve, plus valve travelImmediate colder chilled-water resetA change in weekly lead order5. A terminal meets design airflow but the space remains warm. Which evidence most directly distinguishes an overly warm primary supply from inadequate flow?Only the number of alarmsDamper command without flow feedbackMeasured primary supply temperature together with verified terminal airflow6. An illustrative linear hot-water reset delivers 170°F at 10°F outdoors and 130°F at 50°F outdoors. What is the target at 25°F outdoors?Answer (°F)7. Most VAV dampers throttle near minimum. One terminal requests more pressure, has a wide-open actuator and nearly zero measured flow. What should precede a permanent pressure increase?Verify airflow at that terminal and investigate its branch and flow sensingFix a new high duct-static setpointRecalibrate every transmitter8. Under ideal fan affinity assumptions, what percentage of original shaft power is required at 80% speed?Answer (%)9. At a steady 120 tons, measured total plant input is 96 kW. What is the observed plant efficiency?Answer (kW/ton)Submit assessmentApply this material in Unit 6Diagnose airside deliveryApply this material in Unit 5Determine who owns the commandApply this material in Unit 7Diagnose hydronic deliveryReturn to Learning Center