Module examinationPass at 80%. 1. With 99% actuator feedback, which observation directly tests linkage integrity?A second reading of the same feedback pointA high pump-speed commandValve stem movement during the stroke2. The project tolerance is ±0.5°F. A traceable reference reads 56.4°F and a displayed input reads 57.2°F. What is the signed display-minus-reference error?Answer (°F)3. AI-3 changes correctly but the graphic follows AI-4. What should you check first?The transmitter gainThe graphic object bindingThe duct pressure setpoint4. During a temperature oscillation the valve feedback sticks, then jumps despite smooth requests. What takes priority?Increase the proportional gainHalve the integral timeVerify the actuator and valve movement5. A 90-second full-stroke actuator moves uniformly from 20% to 80%. Estimate its travel time.Answer (s)6. For a linear 4–20 mA, 0–2 in. w.c. transmitter, what should 16 mA indicate?Answer (in. w.c.)7. A 2–10 V actuator is commanded to 75% during checkout. Which combination is the best acceptance evidence?A 75% graphic and a cleared alarmAn 8 V terminal reading, the specified shaft position after travel, the process response and a recorded return to AutoAn 8 V measurement alone8. If proof returns at t=12 then drops at t=19, when should a 30-second continuous-loss alarm first occur?Answer (s)Submit assessmentApply this material in Unit 10Commission a systemReturn to Learning Center