Workshop plan · 32 hours

Supervised BAS workshop

Prepare online, then work through eight bench modules with a qualified instructor. The proposed schedule includes a five-hour commissioning capstone.

Prepare the bench

Start with basic electrical safety, meter use and wiring-diagram skills. The instructor supplies the approved sequence, isolated network, safe test loads, current matching manuals and access to licensed vendor software where needed. Use simulations for behavior the bench cannot safely demonstrate.

Online lesson credit tracks exercises in this browser. Keep separate records for hardware demonstrations, instructor assessment and workshop attendance. This plan does not award field hours or vendor certification.

Eight modules. 32 hours of planned practice.

Module 01 · 3 hours

BAS fundamentals

Map physical equipment, local controller, supervisor, measured inputs, software values and output requests to a sequence of operation.

Bench exercise, tools and evidence

Supervised practice

Identify and label training controllers and trace a simple command-to-proof circuit. Required: a laptop/browser, de-energized controller and I/O demonstration board, matching wiring and point documents, safe low-voltage test supply, a suitable meter and instructor supervision. No licensed engineering tool is required for the identification exercise; any subsequent controller access requires its compatible authorized tool.

Deliverable for review

An annotated architecture sketch and point list separating measurement, command, feedback, proof and process response.

Module 02 · 4 hours

Network protocols and integration evidence

Distinguish BACnet identities, serial addressing and gateway mapping, then verify units, scaling, quality and data freshness across one integration path.

Bench exercise, tools and evidence

Supervised practice

Build and inspect a small isolated RS-485 training trunk, document addresses/baud/termination, and verify a known sensor through a gateway. Required: two compatible BACnet MS/TP training controllers, documented cable and termination, gateway, an appropriate USB/serial interface, meter, and a Modbus training sensor or simulator if that exercise is selected. Use an authorized BACnet discovery/configuration application and any manufacturer gateway software with required licenses. Discovery and wiring changes stay on the instructor's isolated bench network.

Deliverable for review

A network drawing, device/address inventory, point map and comparison of local versus integrated values with units and timestamps.

Module 03 · 4 hours

Vendor architectures and engineering tools

Identify supervisory and equipment-control roles across Trane, Carrier, Honeywell/Niagara and Johnson Controls, then select the correct documentation and compatible tool for one actual training controller.

Bench exercise, tools and evidence

Supervised practice

Inspect one platform, inventory its controller/application versions, read points and locate its backup/restore process. Required: an instructor-provided controller or supported vendor training appliance, matching manuals and network access, and the compatible installed tool with the necessary license and authorized account, such as Niagara Workbench, Tracer TU, a Carrier engineering tool or Metasys SCT/CCT as applicable. A browser front end alone does not demonstrate all engineering functions, and one platform exercise does not establish proficiency on the other vendors.

Deliverable for review

A vendor/tool role matrix plus an equipment-specific access, compatibility and backup checklist for the selected platform.

Module 04 · 6 hours

Programming and bounded sequencing

Test weekly and exception occupancy, input validity, loop direction/limits, permissions and documented protection without confusing software demand with delivered capacity.

Bench exercise, tools and evidence

Supervised practice

Implement or configure a small approved training sequence and exercise normal, exception and invalid-input states before comparing command, feedback and process response. Required: a compatible training controller or supported vendor simulator, two or three sensors or signal simulators, a safe actuator/test load, matching sequence and I/O documents, suitable instruments, and the vendor engineering software with required license. An instructor must approve any protective-function test method; use a simulator when a safe hardware test is unavailable. BAS Bridge's conceptual examples are not executable vendor syntax.

Deliverable for review

A reviewed sequence description, schedule test matrix and trends showing target, measurement, output, mode, quality and limits with expected versus observed results.

Module 05 · 3 hours

Actionable alarms and FDD

Separate a protective trip, an actionable alarm and an analytical fault hypothesis; apply operating-state context, persistence and appropriate escalation.

Bench exercise, tools and evidence

Supervised practice

Use a recorded or simulated startup, command/proof failure and performance-fault dataset to review nuisance alarms and propose bounded alarm/FDD rules. Required: a laptop, instructor-supplied time-aligned point histories and sequence/alarm requirements, plus the isolated training controller if implementing a rule. Implementation requires its compatible licensed configuration tool; demonstrating a vendor analytics product additionally requires that product's licensed training environment. No commercial FDD package is needed to assess the supplied evidence.

Deliverable for review

An alarm rationalization sheet identifying condition, mode, delay/deadband rationale, consequence, owner, action, escalation and return-to-normal evidence, plus an FDD hypothesis and verification plan.

Module 06 · 4 hours

Security and enterprise integration

Draw trust boundaries, identify command ownership and apply authenticated, encrypted connections with maintained certificates and restricted access.

Bench exercise, tools and evidence

Supervised practice

On an isolated test network, document segmentation and roles, validate a certificate-backed connection, and demonstrate a read-only telemetry path with known point quality. Required: an instructor-managed switch/router or virtual lab, supported BACnet/SC nodes and hub for the selected SC demonstration, or an MQTT broker and TLS-capable clients for the telemetry demonstration, test certificates and a laptop. Confirm compatible firmware, drivers and required vendor licenses before the session; Workbench, a protocol driver or a vendor SC feature may require licensing. Use test accounts and instructor-operated credential provisioning; keep the exercise separate from production and public internet exposure.

Deliverable for review

An integration/data-flow drawing, permitted connection list, role matrix, certificate renewal owner and evidence that authorization, encryption and data freshness were checked separately.

Module 07 · 3 hours

Commissioning and troubleshooting

Prove point identity and physical response, locate the first failed boundary, and write acceptance and restoration records against the approved sequence.

Bench exercise, tools and evidence

Supervised practice

Check representative input/output points and perform one bounded functional test with independent measurements. Required: the isolated controller and safe test loads from earlier sessions, matching manuals and approved test sheet, suitable calibrated instruments, and qualified instructor supervision. Any configuration access requires the compatible licensed vendor tool and authorized account. Use simulated evidence for energized, moving-equipment or protective tests that the bench cannot safely support.

Deliverable for review

A completed point-checkout sheet, expected/observed test result, exception record, next-action owner and restoration readback.

Module 08 · 5 hours

Integrated capstone and review

Demonstrate one coherent controller-to-supervisor solution and defend the conclusions with a documented sequence, credible measurements and verified closeout.

Bench exercise, tools and evidence

Supervised practice

Build a mini-BAS with a controller, two or three sensors or simulators, an actuator/test load and one read-only integration path. Demonstrate ordinary and exception occupancy, a normal loop, one invalid input, an approved interlock/protective case, and an actionable alarm or analytical fault check. Required: the instructor-approved hardware and safe network from earlier modules, matching sequence/point/manual documents, instruments, compatible engineering/configuration tools and every required license. The instructor reviews test boundaries and observes the bench assessment; unavailable behavior is recorded as untested rather than passed.

Deliverable for review

A capstone packet containing architecture, tool/version inventory, point map, schedule and sequence, alarm/FDD rationale, access boundary, time-aligned trends, functional test results, exceptions and restoration evidence. Instructor assessment is separate from online quiz credit; the plan makes no claim of earned field hours or vendor certification.

Capstone review

Have the instructor mark each area as demonstrated, needs correction or untested. An unavailable seasonal condition stays untested until it can be observed.

  1. Architecture and point meaning. Trace the local controller, supervisor, gateway, identities, units, quality and timestamps.
  2. Control intent. Check ordinary and exception schedules, valid-input behavior, permissions, limits and protective boundaries against the approved sequence.
  3. Alarm and FDD response. Document prerequisites, persistence, clearing behavior, responsible owner and next discriminating test.
  4. Integration security. Provide evidence of necessary routes, account roles, certificate ownership and communication-loss behavior.
  5. Functional result and closeout. Record expected and observed states, timing, independent measurements, open deficiencies and restoration.
Prepare checkout, trends and handoff →All learning tracks →