Resolve ambiguous control-room language by identifying the actual source, action or measured result.

Frequently used terms

Frequently used terms
TermField meaning
CommandThe effective instruction issued to a device. Compare it with actual travel, rotation or flow.
ProofAn observation satisfying a defined criterion. A current switch proves current above its threshold. A duct switch proves pressure differential at its taps.
PermissiveA condition the sequence requires before an action, such as a ready input before a fan start.
InterlockA dependency that allows, inhibits or stops another function. Document whether it prevents startup, interrupts operation, or both.
SetpointThe active target after applicable schedules, resets, limits and priority selection.
Process variableThe measured quantity the loop regulates, such as discharge temperature or duct static pressure.
DeadbandAn interval in which specified actions are inactive, such as the temperature range between heating and cooling calls.
HysteresisDifferent switching thresholds for a rising and falling signal. Between thresholds the prior state matters.
SaturationThe controller has reached its output limit. Additional error cannot increase output in that direction.
Stale valueA previously valid sample whose age exceeds the application’s usable interval. Check timestamps and quality.
BiasA systematic difference between a measurement and a suitable reference under comparable conditions.
FeedbackA returned observation such as position or speed. Locate the pickup to see which part of the mechanism it represents.

Field example

A technician reports “fan proven.” Ask which device supplied proof, when it changed, and whether an independent airflow measurement agrees.