Equipment troubleshooting flowcharts

Choose the next branch from a measured condition when a fan has no airflow or a coil has no heat.

Branch by the first failed observation

Branch by the first failed observation
DecisionIf yesIf no
No airflow · valid fan start request?Inspect effective drive permission and control source.Trace schedule, setpoint, interlocks and priority.
Drive accepts run with a nonzero speed reference?Verify motor and fan-wheel movement independently.Compare relay, input state, drive faults and programmed limits.
Fan wheel turns in expected direction?Check duct path, dampers, filter drop and delivered flow.Trace coupling or belt, drive output and actual shaft motion.
No coil heat · water hot at branch inlet?Check measured water flow and valve/stem response.Trace plant temperature and isolation up to the branch.
Hot water flows through the coil?Compare entering/leaving air and water temperatures at steady airflow.Check available differential pressure, valve authority, restrictions and air in the branch.
Measured air temperature rises across the coil?Trace distribution, zone demand and the original complaint.Check load, air bypass, sensor placement and heat-transfer surface.

Field example

A seized fan relay and a broken belt both produce loss of airflow. Drive acceptance followed by a rotating motor and stationary wheel supports the belt branch. An absent drive permission supports an upstream control-circuit investigation.