Control and verification
Equipment troubleshooting flowcharts
Choose the next branch from a measured condition when a fan has no airflow or a coil has no heat.
Branch by the first failed observation
| Decision | If yes | If no |
|---|---|---|
| No airflow · valid fan start request? | Inspect effective drive permission and control source. | Trace schedule, setpoint, interlocks and priority. |
| Drive accepts run with a nonzero speed reference? | Verify motor and fan-wheel movement independently. | Compare relay, input state, drive faults and programmed limits. |
| Fan wheel turns in expected direction? | Check duct path, dampers, filter drop and delivered flow. | Trace coupling or belt, drive output and actual shaft motion. |
| No coil heat · water hot at branch inlet? | Check measured water flow and valve/stem response. | Trace plant temperature and isolation up to the branch. |
| Hot water flows through the coil? | Compare entering/leaving air and water temperatures at steady airflow. | Check available differential pressure, valve authority, restrictions and air in the branch. |
| Measured air temperature rises across the coil? | Trace distribution, zone demand and the original complaint. | Check load, air bypass, sensor placement and heat-transfer surface. |
Field example
A seized fan relay and a broken belt both produce loss of airflow. Drive acceptance followed by a rotating motor and stationary wheel supports the belt branch. An absent drive permission supports an upstream control-circuit investigation.
Practice and related lessons
- Work a no-airflow call
- Localize a shutdown across electrical and mechanical systems
- Prove damper and valve travel under load
- Read a drive from speed reference to delivered air
- Airside dispatch · persistent duct pressure requests
- Plant dispatch · cold perimeter on a hot header
- Reconstruct an intermittent failure from trends and alarms
Technical references
- DOE FEMP · Commissioning for Federal Facilities
- Belimo · Globe valve flow paths and fail positions
- Belimo · LF24-SR US actuator technical data
- ASHRAE Handbook · Hydronic heating and cooling
- U.S. DOE · Fan system affinity laws
- Trane · High-Performance Sequences of Operation
- Caleffi idronics 32 · Troubleshooting Hydronic Systems
- Johnson Controls · Alarm and event management overview
- Johnson Controls · Trend Automator application note