What you’ll learn
- Identify the indoor supply and condenser air paths.
- Verify cooling across the occupied-air section.
Before you start · 1 related lesson
0 of 1 prerequisites demonstrated. You can open this lesson at any time.What the equipment does
A packaged rooftop unit (RTU) houses several components in one outdoor cabinet. The training unit uses mechanical refrigeration to cool building air. Its indoor blower circulates air into the duct. Its separate outdoor Heat exchanger where refrigerant rejects heat and condenses. fan moves air across a coil that releases heat outdoors.
Follow the physical path
Trace room return and outdoor ventilation air into the mixing section. Follow the mixed air through the filter and indoor coil to the supply duct. Outside this duct path a second stream cools the condenser and returns outdoors. In suitable weather some units use more outdoor air for cooling, a strategy called economizing.
Supply air · example packaged unit
Outdoor heat rejection
Intake · In this example a rooftop mixing section admits outdoor air.
Normal operation
Example training conditions
- During mechanical cooling with the blower running, mixed air 77°F becomes 58°F supply air.
- Outdoor air entering the condenser at 88°F leaves that section warmer. The condenser exhaust remains outdoors.
Worked service example
A roof observer sees a turning fan and reports the room must be receiving air.
Recorded field evidence · training example
- Condenser fan rotates.
- Supply blower status unavailable. A calibrated hood measures 0 cfm at the affected outlet.
- Other outlets have not been checked.
The roof observation concerns a different air stream. The outlet measurement establishes local loss of delivery. Inspect supply blower status and additional branches to distinguish a unit-wide loss from a local blockage.
Terms in this lesson
- Packaged unit
- Equipment assembled together in one cabinet.
- Condenser
- Heat exchanger where refrigerant rejects heat and condenses.
Hands-on exercise
Read the two air paths during a rooftop cooling request.
Predict before inspection
Standalone simulator · free practice
Inspect RTU-01
Separate the mixed-air and supply sections from the outdoor condenser.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Identify which fan and which air stream a measurement actually describes.
References and further reading
- Pacific Northwest National Laboratory · Unitary HVAC equipment ↗
- Danfoss · An introduction to walk-in coolers ↗