What you’ll learn
- Trace return and outdoor air to the supply duct.
- Choose measurements that distinguish central cooling from local delivery.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.What the equipment does
An air-handling unit (AHU) prepares and moves air for several occupied areas. A return duct carries some room air back. An outdoor intake can introduce ventilation air. A mixing section combines the streams, a filter captures particles, coils change the air temperature and a fan moves it. The installed arrangement determines where the fan sits relative to the coils.
Follow the physical path
In the training office, AHU-01 supplies a common duct that branches to the conference terminal. Find the mixed-air temperature before the active coil and the discharge-air temperature after conditioning. A thermometer measures temperature at its own location. To establish delivery at a seat, continue downstream to the branch.
Supply air · example draw-through unit
Coil water · separate from air
Mixed air · Outdoor and return air join in the mixing chamber.
Normal operation
Example training conditions
- Occupied cooling with steady airflow. Mixed air is 76°F, discharge air is 56°F and the conference branch carries 450 cfm.
- A 20°F drop across the conditioning section is evidence of cooling at this load. The measured branch flow confirms some air arrives.
Worked service example
One conference room warms while other zones feel normal.
Recorded field evidence · training example
- Mixed air 75°F; AHU discharge 55°F.
- Conference branch 95 cfm against a 400 cfm request.
- A neighboring branch measures 405 cfm against a 400 cfm request.
The AHU supplies cool air and a neighbor receives its requested volume. Localize the conference shortage by measuring pressure and airflow at that terminal. The discrepancy cannot by itself identify a stuck damper.
Terms in this lesson
- Return air
- Air coming back from occupied spaces.
- Discharge air
- Air leaving the equipment at the indicated measurement location.
Hands-on exercise
Trace a second occupied cooling record from mixing box to branch.
Predict before inspection
Standalone simulator · free practice
Inspect AHU-01
Locate entering air, the cooling section, the fan and the discharge reading.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Start with the common supply and follow the branch serving the complaint.
References and further reading
- DOE and PNNL · Operations and Maintenance Best Practices, chapter 9 ↗
- Pacific Northwest National Laboratory · Variable air volume systems ↗