Level 1 · Commercial HVAC equipment anatomy

Inside the air-handling unit

12 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Trace return and outdoor air to the supply duct.
  • Choose measurements that distinguish central cooling from local delivery.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

What the equipment does

An air-handling unit (AHU) prepares and moves air for several occupied areas. A return duct carries some room air back. An outdoor intake can introduce ventilation air. A mixing section combines the streams, a filter captures particles, coils change the air temperature and a fan moves it. The installed arrangement determines where the fan sits relative to the coils.

Follow the physical path

In the training office, AHU-01 supplies a common duct that branches to the conference terminal. Find the mixed-air temperature before the active coil and the discharge-air temperature after conditioning. A thermometer measures temperature at its own location. To establish delivery at a seat, continue downstream to the branch.

Follow the equipment pathsSelect a component to inspect its function.

Supply air · example draw-through unit

Coil water · separate from air

Mixed air · Outdoor and return air join in the mixing chamber.

Normal operation

Example training conditions

  • Occupied cooling with steady airflow. Mixed air is 76°F, discharge air is 56°F and the conference branch carries 450 cfm.
  • A 20°F drop across the conditioning section is evidence of cooling at this load. The measured branch flow confirms some air arrives.

Worked service example

One conference room warms while other zones feel normal.

Recorded field evidence · training example

  • Mixed air 75°F; AHU discharge 55°F.
  • Conference branch 95 cfm against a 400 cfm request.
  • A neighboring branch measures 405 cfm against a 400 cfm request.

The AHU supplies cool air and a neighbor receives its requested volume. Localize the conference shortage by measuring pressure and airflow at that terminal. The discrepancy cannot by itself identify a stuck damper.

Terms in this lesson
Return air
Air coming back from occupied spaces.
Discharge air
Air leaving the equipment at the indicated measurement location.

Hands-on exercise

Trace a second occupied cooling record from mixing box to branch.

Predict before inspection

If the central coil cools flowing air, which comparison should show a drop?

Knowledge check

Pass at 80%.

1. Which section removes particles from the air?
2. Which stream enters from outdoors?
3. Which reading tests the complaint that air never reaches one room?
4. All branches receive warm air while mixed and discharge temperatures match during a cooling request. Where would you check next?
5. Mixed air is 79°F and discharge is 58°F. Find the temperature drop.

Field takeaways

  • Start with the common supply and follow the branch serving the complaint.