What you’ll learn
- Trace replacement air through a room to the exhaust outlet.
- Distinguish a run indication from a measured exhaust volume.
Before you start · 1 related lesson
0 of 1 prerequisites demonstrated. You can open this lesson at any time.What the equipment does
An exhaust fan removes air and the moisture, odors or contaminants it carries. Replacement air must enter the space through a designed supply or transfer path. A closed-off room can restrict exhaust even if the fan rotates.
Follow the physical path
Trace replacement air into the room, into the exhaust grille, along the duct and outdoors. A fan command requests operation. A run contact might indicate motor operation. A hood or duct measurement quantifies the actual air removed at the test point.
Exhaust air
Room · Air enters the occupied space. Measure conditions where people experience them.
Normal operation
Example training conditions
- Occupied exhaust request on; local run contact closed and grille flow 300 cfm at the accepted condition.
- The modeled fan EF-01 serves this exhaust path. The inlet transfer opening is available.
Worked service example
A restroom has lingering odors while the fan graphic is green.
Recorded field evidence · training example
- Motor run contact closed.
- Measured grille flow 90 cfm against an accepted 300 cfm.
- Room door is difficult to pull open while exhaust is enabled.
Air removal is low and the room may be strongly negative to its neighbor. Check the replacement-air path and measure the room pressure difference. Also inspect duct resistance and the fan. The door observation alone cannot quantify pressure.
Terms in this lesson
- Makeup air
- Air entering to replace air removed by exhaust.
- Run proof
- A separate indication meeting a defined condition, such as measured motor current.
Hands-on exercise
Compare two recorded room configurations at the same fan command.
Predict before inspection
Standalone simulator · free practice
Inspect EF-01
Compare the effective request, fan proof and exhaust flow.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Verify replacement air as well as the exhaust outlet.