What you’ll learn
- Calculate pump pressure rise.
- Distinguish circulation in a header from circulation at a distant coil.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.What the equipment does
A hydronic pump adds mechanical energy to water so it can circulate through piping and coils. In a centrifugal pump, a rotating impeller transfers energy to the liquid. The flow that results depends on pump speed, the pump curve and resistance of the connected system.
Follow the physical path
Trace the pump The inlet side of a pump. , A common outlet pipe feeding one or more branches. , branch valve, coil and return. Pressure difference between pump taps can provide pump head information when interpreted with the equipment curve, elevation and velocity. An independent branch flow reading answers the more specific question of how much reaches that coil.
Water branch · closed loop
Pump suction · Water reaches the pump inlet from the return path.
Normal operation
Example training conditions
- Pump running at its training operating point. Suction 15 psi and discharge 23 psi at comparable elevations and pipe velocities.
- Header meter 45 gpm. The conference branch receives 4 gpm while heating is required.
Worked service example
The pump is on but the conference reheat coil has little heat.
Recorded field evidence · training example
- Pump differential 8 psi, matching a previous acceptable period.
- Another active branch receives 5 gpm. Conference branch reads 0 gpm.
- The conference control valve request is 90%.
A pressure rise and one healthy branch show the pump is doing work somewhere. Verify the conference valve and the pressure available at this branch, then confirm branch flow. A header observation cannot locate the restriction.
Terms in this lesson
- Suction
- The inlet side of a pump.
- Discharge header
- A common outlet pipe feeding one or more branches.
Hands-on exercise
Compare the pump and two branches before changing speed.
Predict before inspection
Standalone simulator · free practice
Inspect a heating-water pump
Compare pump request, speed and flow available to the heating circuit.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Locate the measured flow relative to the affected load.